Product Details
Advantages
Robust design
Fine fibre ensures that filter maintains its efficiency throughout its life in the system
Individually tested according to EN 1822
Application
Built-up filter banks, split systems, free-standing units.
EN1822:2009 filter class:
E11(EN1822), ≥95% at MPPS
E12(EN1822), ≥99.5% at MPPS
H13(EN1822), ≥99.95% at MPPS
H14(EN1822), ≥99.95% at MPPS
Recommended final pressure drop: 500 Pa.
Temperature: 90℃ maximum in continuous service.
Thickness vs Efficiency vs Pressure drop
Thickness |
Plait |
Pressure drop@0.8/s/Pa |
(inches) |
(mm) |
(mm) |
E11 |
E12 |
H13 |
H14 |
6 |
150 |
3 |
165 |
185 |
200 |
215 |
5 |
180 |
205 |
220 |
235 |
8 |
200 |
225 |
250 |
260 |
9
|
220
|
3 |
150 |
165 |
180 |
195 |
5 |
160 |
185 |
200 |
210 |
8 |
180 |
200 |
225 |
235 |
Dimensions vs Air flow
Dimensions (HxW) |
Air flow
m³/Hr@0.45m/s |
(inches) |
(mm) |
24X12 |
610x305 |
290 |
24x24 |
610x610 |
580 |
24x22 |
595x287 |
260 |
24x24 |
595x595 |
550 |
Note: Pressure drop +/-15% Odd sizes available
Model named rule:
CFOP-①-② X ③X ④-⑤⑥/⑦⑧
Remarks:
①-Efficiency level(E11-H14)
②-Height dimension H(mm)
③-Width dimension W(mm)
④-Depth frame D(mm)
⑤-up side
1:sealing gasket
0:none
⑥-down side
1:sealing gasket
0:none
⑦-down side
1: face guard
0: none
⑧-up side
1: face guard
0: none
http://www.aif-filter.com/