Product Details
First of all thank you for using our meter, This manual contains instructions for the installation of meters, operations, parameter setting in the PC.
Safety fence is a new type of meter that our Company recently developed, using photoelectric isolation technology, SMT manufacturing process and international standards DIN Rail installation, and have a wide voltage, small size, long life, easy-to-install, and strong anti-interference, and other advantages. Instrumentation is for a group of signal input, two groups simultaneous signal output, communication using ModBus agreement, through RS-485 interface with the PC or PLC-controlled part on-line to concentrate on monitoring and control meters, in connection with the PC Meter can amend the parameters through PC.
1. Input type: CU50\PT100\K\E\J\T\S\R\WR25\N\F2\0-5V\1-5V
2. Output precision: 0.5%F. S
3. Output signal: Two group 4~20mA(adjustable through parameter OUTH\OUTL)
4. Overall dimension(mm): 106× 76× 25
5. Power supply: AC 85~242V 50/60Hz
6. Working circumstance: Temperature 0~50, humidity85%RH without.
Corrode and strong electromagnetism disturb.
Series |
code |
Name |
Remark |
Setting range |
Ex-Factory |
1 |
Pb |
Sensor error amendment |
The sensor have deviation can use item to revisal |
0~±20.0 |
0.0 |
2 |
FILT |
Filt modulus |
The first order lag filter coefficient, the value is greater, the performance anti-jamming moment is stronger, but the response time lag. The pressure and flow control of its value should be smaller, temperature and level control should be relatively large |
0~50 |
20 |
3 |
OUTH |
Allow exports max value |
Restrain maximum value of adjust output. |
outL~2200 |
2000 |
4 |
OUTL |
Allow exports min value |
Restrain minimum value of adjust output |
0~outH |
400 |
5 |
LocK |
Code lock |
0-all the parameter can be revised 1-only the SP can be revised |
0~50 |
0 |
6 |
Sn |
Input type |
'0'Cu50 -50.0~150.0ºC; '1'Pt100 -199.9~200.0ºC; '2'Pt100 -199.9~600.0ºC; '3'K -30.0~1300ºC; '4'E -30.0~700.0ºC ; '5' J -30.0~900.0ºC; '6'T -199.9~400.0ºC; '7' S -30~1600ºC; '8' R -30.0~1700.0ºC; '9' WR25 -30.0~2300.0ºC; '10' N -30.0~1200.0ºC; '11' Idiosyncratic type ; '12' 0~5V(0~10mA); '13' 1~5V(4~20mA) |
0~13 |
random |
7 |
P-SH |
Display the high limit |
P-SH decide the display range, the value and unit are decided by factory and client freely. |
P-SL~9999 |
random |
8 |
P-SL |
Display the low limit |
P-SL decide the display range, the value and unit are decided by factory and client freely. |
-1999~P-SH |
random |
9 |
Addr |
Communication addres |
The meter's number in the control system |
0~63 |
0 |
10 |
BAud |
Communication baud rate |
'0'1200;'1'2400; '2'4800; '3'9600 |
0~3 |
9600 |